Inductive Conductivity Transmitter – FLS C6.30
The FLS C6.30 is a family of inductive conductivity transmitters designed with a two-wire 4-20mA output integrated directly into the sensor. This innovative technology makes it ideal for a broad range of applications, particularly for measuring high conductivity values up to 1000 mS in aggressive fluids, as the only wetted material is C-PVC. With no electrodes in direct contact with the liquid, the C6.30 ensures reliable, stable, and long-term performance. A built-in Pt100 sensor provides accurate Automatic Temperature Compensation (ATC), enhancing precision across varying conditions. The isolated 4-20mA output allows seamless direct connection to PLCs or data loggers without requiring additional interfaces. Both the transmitter and temperature sensor are factory calibrated, guaranteeing accuracy and simplifying installation.
Inductive Conductivity Transmitter – FLS C6.30
- Corrosion & coating resistant
- Compact transmitter
- No calibration required
- Easy installation
- PT100 sensor integrated
- Suitable for submersible installation
Technical Details of Inductive Conductivity Transmitter – FLS C6.30
| Specification | Details |
|---|---|
| Body Material | C-PVC |
| Body Length | 207 mm |
| Enclosure | IP68 |
| Power Supply | 10–30 VDC regulated |
| Max Power Consumption | < 22 mA |
| Max Working Pressure / Working Temperature | – 10 bar (145 psi) @ 25°C (77°F) – 6 bar (87 psi) @ 50°C (122°F) |
| Process Connection | 1 ½” male NPT |
| Manufactured under | ISO 9001, ISO 14001 |
| Certifications | CE, RoHS Compliant, EAC |
| Part No. | Description / Name | Applications / Operative Range | Cell Constant | Connection | Installation | Weight (gr.) |
|---|---|---|---|---|---|---|
| C6.30.01 | C-PVC Inductive Conductivity Transmitter with Temperature Sensor included | 0–10 mS/cm | - | 3 m | 1 1/2” NPT male threaded | 550 |
| C6.30.02 | C-PVC Inductive Conductivity Transmitter with Temperature Sensor included | 0–100 mS/cm | - | 3 m | 1 1/2” NPT male threaded | 550 |
| C6.30.03 | C-PVC Inductive Conductivity Transmitter with Temperature Sensor included | 0–1000 mS/cm | - | 3 m | 1 1/2” NPT male threaded | 550 |
1 – Cable: 3 mt (9 ft.)
2 – 1 ½” male NPT
3 – C-PVC coating

Customization & Processing Options
Customizations Option Available for Inductive Conductivity Transmitter – FLS C6.30
At Petron Thermoplast, we offer customized PVDF fittings to meet your specific system requirements.
Customization options include:
- Tailor-made dimensions and wall thicknesses
- Custom-molded and machined PVDF fittings
- Pre-fabricated manifolds and assemblies
- Choice of connection type (butt fusion, socket fusion, or flanged)
- OEM branding or marking options